Introduction

XY800 series explosion-proof oil tank monitor is a monitor that display tank level data through the touch operating screen. It can be connected with liquid level meters, thermometers, pressure transmitters and alarm equipment directly and display the instrument parameters; it also can communicate with the management system of the oil tank, and display all kinds of instrument parameters and alarm by using remote projection. With all these performance, this type of monitor meets monitoring display requirement for all kinds of storage tanks, and make it easy for operators to acquire information of tank level, temperature, pressure data and etc., which make the monitor widely applied in safety monitoring system and automation system at harsh and hazardous locations in Petroleum, Petrochemical, Light Textile, Pharmaceutical, Metallurgy and Electricity industries.

 

Features

  • High brightness, colorful monitoring interface
  • Support single tank/ double tanks monitoring, four tanks monitoring at most at the same time
  • Support direct connection with analog output (4-20mA) field instruments
  • Support direct connection with field instruments that use Modbus protocol to communicate
  • Support direct connection with management system server through Ethernet, display the storage tank data via remote client
  • Military rank wide-range temperature design, can be used in harsh environment, such as hyperthermia and alpine locations.
  • Application: suitable for hazardous environment in Zone 1 and Zone 2.

 

Technical Specification

Screen size

7”, 10.4” TFT LCD

Resolution

800x480/ 800x600

Color

65536

Brightness

>300 cd/m²

Backlit

LED

Ethernet

1*10M/ 100M/ 1000Mbps

Serial Communication connector

2*RS485, support Modbus protocol

 

Operating Environment

Operating Temperature

Normal: -20~60 °C; Wide: -40~70 °C

Storage Temperature

Normal: -30~80 °C; Wide: -40~80 °C

Humidity

10~90% RH(no condensing)

 

Electric parameter warning! There will be damages caused by over ranged voltage or inversed wiring of positive and negative poles.

 

Rated power consumption

5W, Max 15W

Rated voltage

DC24V, workable range: DC18V ~ DC32V

Electrical connector

3*1/2” explosion-proof sealed joints

Explosion-proof class

ExdibIIB+H2T6

Payment Terms︰ TT/Western Union/LC